Example: Design Current for the R-TPN Load of Max 10 KW value is 20.89 A
We need to select the Next Higher size of Breaker available in the Market for Calculated Design Current (=20.89 A)Here In our Case 30/32 A breaker can be selected. It can be MCCB or MCB or RCBO depending upon requirements.
Ib = 21 A
In = 30 A
Iz = 52.48 (From Cable Data)
Note: The operating characteristics of a device protecting a conductor against overload shall satisfy the following two conditions:
Ib <= In <= Iz
I2 <= 1.45 Iz
- Ib = the current for which the circuit is designed, e.g. maximum demand
- In = the nominal current of the protective device
- Iz = the continuous current-carrying capacity of the conductor (see the AS/NZS 3008.1)
- I2 = the current ensuring the effective operation of the protective device and may be taken as equal to either—
- (a) the operating current in conventional time for circuit breakers (1.45 In); or
- (b) the fusing current in conventional time for fuses (1.6 In for fuses by the IEC 60269 series)
Criteria for type gG fuses - Comply with the IEC
Standard requirement I2 ≤ 1.45 Iz:
As per the IEC standard, condition I2 ≤ 1.45 Iz must be taken into account, where l2 is the fusing (melting level) current, equal to k2 x In (k2 ranges from 1.6 to 1.9) depending on the particular fuse concerned.
In such a case an extra factor
k3 = 1.31 for fuses with In < 16A, or k3 = 1.1 for fuses with In ≥ 16A is considered,
so that 12 ≤ 1.45 Iz will be valid if In s Iz/k3.
"In Simple Words, We should consider these 2 conditions so that the conductor will not be overheated or burned before the breaker trips."
We can Select Cable Size based on Breaker selection directly because it keeps the account of conductor Ampacity in the worst-case scenario. Or we can select Cable from the Manufacturer Data table as well.
If MCCB = 10 Then CABLE = "1 x 4 mm2"
If MCCB = 20 Then CABLE = "1 x 6 mm2"
If MCCB = 30 Then CABLE = "1 x 10 mm2"
If MCCB = 40 Then CABLE = "1 x 16 mm2"
If MCCB = 60 Then CABLE = "1 x 25 mm2"
If MCCB = 80 Then CABLE = "1 x 35 mm2"
If MCCB = 100 Then CABLE = "1 x 50 mm2"
If MCCB = 125 Then CABLE = "1 x 50 mm2"
If MCCB = 150 Then CABLE = "1 x 70 mm2"
If MCCB = 175 Then CABLE = "1 x 70 mm2"
If MCCB = 200 Then CABLE = "1 x 95 mm2"
If MCCB = 225 Then CABLE = "1 x 95 mm2"
If MCCB = 250 Then CABLE = "1 x 120 mm2"
If MCCB = 275 Then CABLE = "1 x 120 mm2"
If MCCB = 300 Then CABLE = "1 x 150 mm2"
If MCCB = 325 Then CABLE = "1 x 150 mm2"
If MCCB = 350 Then CABLE = "1 x 185 mm2"
If MCCB = 350 Then CABLE = "1 x 240 mm2"
If MCCB = 375 Then CABLE = "1 x 240 mm2"
If MCCB = 400 Then CABLE = "1 x 300 mm2"
If MCCB = 450 Then CABLE = "1 x 300 mm2"
If MCCB = 500 Then CABLE = "1 x 400 mm2"
If MCCB = 500 Then CABLE = "2 x 120 mm2"
If MCCB = 600 Then CABLE = "2 x 150 mm2"
If MCCB = 700 Then CABLE = "2 x 185 mm2"
If MCCB = 750 Then CABLE = "2 x 240 mm2"
If MCCB = 800 Then CABLE = "2 x 300 mm2"
If MCCB = 900 Then CABLE = "2 x 300 mm2"
If MCCB = 1000 Then CABLE = "2 x 400 mm2"
In Our Example, We can select a "1 x 10 mm2" Cable. that will fulfil all the conditions required.
Several major factors can affect voltage drop in an electrical system. These include:
Cable length: Voltage drop is directly proportional to the length of the cable. The longer the cable, the greater the voltage drop.
Cable size: The size of the cable's cross-sectional area affects its resistance. Larger cables have less resistance and therefore less voltage drop.
Current: Voltage drop is directly proportional to the current flowing through the cable. Higher currents result in higher voltage drops.
Cable material: The type of material used in the cable affects its resistance. Copper has lower resistance than aluminium, for example, resulting in less voltage drop in a copper cable.
Temperature: The temperature of the cable affects its resistance, and therefore its voltage drop. Higher temperatures increase resistance, resulting in higher voltage drop.
Voltage Drop = (vdFactor / No. of Runs of cable) * Current* (Length Of cable / 1000))) / 415)
"Voltage Drop for 600/1000 V XLPE Insulated Cables in V/A/KM for 3 and 4 Core Cables"
If SizeC = "1.5" Then vdFactor = 26.7
If SizeC = "2.5" Then vdFactor = 16.4
If SizeC = "4" Then vdFactor = 10.2
If SizeC = "6" Then vdFactor = 6.8
If SizeC = "10" Then vdFactor = 4#
If SizeC = "16" Then vdFactor = 2.5
If SizeC = "25" Then vdFactor = 1.65
If SizeC = "35" Then vdFactor = 1.15
If SizeC = "50" Then vdFactor = 0.87
If SizeC = "70" Then vdFactor = 0.6
If SizeC = "95" Then vdFactor = 0.45
If SizeC = "120" Then vdFactor = 0.37
If SizeC = "150" Then vdFactor = 0.3
If SizeC = "185" Then vdFactor = 0.26
If SizeC = "240" Then vdFactor = 0.21
If SizeC = "300" Then vdFactor = 0.19
If SizeC = "400" Then vdFactor = 0.17
If SizeC = "500" Then vdFactor = 0.16
So for a "1 x 10 mm2" 1-Run Cable of 100-meter length with VD factor of 4 V/A/KM, the Voltage Drop is 1.68 % = 6.972 Volts."
If the Supply Voltage is 415 volts, the terminal voltage is at (415-6.972) volts = 408 volts.
MEW Kuwait - The maximum permissible drop in voltage from the consumer’s terminal to any
point to his installation shall not exceed 2.5% of the nominal voltage when the conductors
are carrying full load current (6 volts for 1 phase and 10 volts for 3 phase systems).
Isc = V / [(Zc x √3) x N]
where:
- Isc = the short circuit current in amperes
- V = the voltage of the power system in volts
- Zc = the total impedance of the cable run in ohms, calculated as Zc = √(R^2 + X^2), where R is the resistance in ohms per unit length of the cable, X is the reactance in ohms per unit length of the cable and √ is the square root function
- N = the number of parallel cable runs
- √3 = the square root of 3, which is a constant factor in three-phase power systems
If we have the Resistance and Reactance values of the cable from the Vendor catalogue, we can use that directly. Or
Generalise Value :
Rmcb = (LENGTH * (1 / 56) * 1000) / (Cable Size * NUMBER OF CABLE)
Xmcb = 0.08 * LENGTH
Rtotal = 0.054 + 1.141 + 0.149 + Rmcb + 7.143
Xtotal = 0.539 + 6.357 + 1.6 + Xmcb + 0.8
Ztotal = ((Rtotal ^ 2) + (Xtotal ^ 2)) ^ 0.5
So, Short Circuit Value will Be 1.28 kA for the above-mentioned values.
Comments
Post a Comment