Posts

Showing posts from May, 2023

TT Earthing System - Must be RCD Protected

Image
411.5 TT system In this system, all exposed-conductive-parts and extraneous-conductive-parts of the installation must be connected to a common earth electrode. The neutral point of the supply system is normally earthed at a point outside the influence area of the installation earth electrode but need not be so. The impedance of the earth fault loop therefore consists mainly in the two earth electrodes (i.e., the source and installation electrodes) in series, so that the magnitude of the earth fault current is generally too small to operate overcurrent relays or fuses, and the use of a residual current operated device is essential. "BS 7671, 411.5.l Every exposed-conductive-part which is to be protected by a single protective device shall be connected, via the main earthing terminal, to a common earth electrode. However, if two or more protective devices are in series, the exposed-conductive-parts may be connected to separate earth electrodes corresponding to each protective devic