TT Earthing System - Must be RCD Protected
411.5 TT system
In this system, all exposed-conductive-parts and extraneous-conductive-parts of the installation must be connected to a common earth electrode. The neutral point of the supply system is normally earthed at a point outside the influence area of the installation earth electrode but need not be so. The impedance of the earth fault loop therefore consists mainly in the two earth electrodes (i.e., the source and installation electrodes) in series, so that the magnitude of the earth fault current is generally too small to operate overcurrent relays or fuses, and the use of a residual current operated device is essential.
"BS 7671, 411.5.l Every exposed-conductive-part which is to be protected by a single protective device shall be connected, via the main earthing terminal, to a common earth electrode. However, if two or more protective devices are in series, the exposed-conductive-parts may be connected to separate earth electrodes corresponding to each protective device.
- The neutral point or the midpoint of the power supply system shall be earthed.
- 411.5.2 one or more of the following types of protective devices shall be used, the former being preferred:
- (i) An RCD
NOTE 1: An appropriate overcurrent protective device may be used for fault protection provided a Suitably low value of Zs is Permanently and reliably assured."
- (ii) An overcurrent protective device
In simple terms, international regulations recommend the use of an RCD-protected TT earthing system. Let's see why?
Installation without RCD:
By applying ohms law,3.8 x 0.5 = 1.9 Volt3.8 x 0.01 = 0.038 Volt3.8 x 0.1 = 0.38 Volt3.8 x 60 = 228 VoltTotal = 230 Volt
Installation with RCD:
Another consideration of Touch Voltage:
411.5.3 Where an RCD is used for fault protection the following conditions shall be fulfilled:
(i) The disconnection time shall be that required by Regulation 411.3.2.2 or 411.3 2.4 and
(ii) Ra x IΔn ≤ 50 V
where:
RA is the sum of the resistances of the earth electrode and the protective conductor connecting it to the
exposed-conductive-parts (in ohms)
IΔn is the rated residual operating current of the RCD.
The requirements of this regulation are met if the earth fault loop impedance of the circuit protected by the RCD meets the requirements of Table 41.5
NOTE 1: Where selectivity between RCDs is necessary refer also to Regulation 536.4.1.4
NOTE 2: Where RA is not known, it may be replaced by Zs
Example:
The resistance of the earth electrode of substation neutral Rn is 10 Ω.The resistance of the earth electrode of the installation RA is 20 Ω.
The earth-fault loop current Id = 231 V / (10+20) Ω = 7.7 A.
The fault voltage Uf = Id x RA = 7.7 x 20 = 154 V and therefore dangerous, but for touch voltage of 50 Volts, IΔn ≤ 50/20 = 2.5 A so that a standard 300 mA RCD will operate in about 30 ms without intentional time delay and will clear the fault where a fault voltage exceeding appears on an exposed-conductive-part.
But In case if RA > 200 Ω , IΔn ≤ 50/200 = 0.25 AThis Means, 300 mA tripping device will fail to protect.So, Earthing resistivity test of Earth Electrode connected to metal case, or body earthing must have resistance less than 200 Ω in all-weather condition.
Note: - ELR with Shunt Trip Circuit Breaker or Audio-Visual Alarm Can also be used as per site condition.
The choice of sensitivity of the residual current device is a function of the resistance RA of the earth electrode for the installation, and is given in Fig.
Comments
Post a Comment